fiberplex FAK-2982-ST Fire Alarm Kit without Strobe
A complete bundled package for Fire Alarm annuciation applications. Does not include warning strobe.
 The unit can be used in areas of high electrical noise or in and out of RF shielded enclosures.
 The fiber optic cable is not susceptible to interference caused by impulse noise, crosstalk, or EMI.
 Privacy of communications is also enhanced because the fiber optic cable does not radiate any emissions. In addition, fiber optic cable offers much longer transmission distances than copper wiring. Multimode optics on the units can extend the distance to 2km.
Key Features
- FOI-2981: Optical Transmitter
 2 Audio Inputs
 1 Doorbell Input
- FOI-4982: Optical Receiver
 2 Audio Outputs
 (8 Ohm and 600 Ohm)
- ADP-2982: Amplified Speaker without Strobe
- PSQ-2910: Power Supply for FOI-2981
- WMA-3002: Wall Mount Adapter for FOI-2981
- FC-VM2TT1-0-8: Fiber Cable, Multimode, Simplex, ST-ST, 8 meter
Technical Specifications
ADP-2982
 Power Requirement: 120/240 VAC, 50/60 Hz
 Input Connector: RCA Type Phono Jack
 Input Impedance: 50 k Ohms
 Output Connector: RCA Type Phono Jack
 Output Impedance: 600 Ohms
 Output Signal Level: 100 mV
 FOI-2981-ST
 Power Requirement: 9 VDC @ 275 mA
 Frequency Response: 100 Hz - 8 kHz ± 3 dB
 Doorbell Operation for C: A doorbell buzzer is generated when this input is grounded.
 Priority Scheme: A (highest - overides B and C), C (overides B), B (lowest)
 Interface Connector: A, B, and C: RCA Type Phono Jack
 FOI-4982-ST
 Power Requirement: 9 VDC @ 275 mA
 AUDIO OUTPUT 8 OHM Interface Connector: 2-Conductor 1/4” Enclosed Telephone Jack (Balanced
 Output)
 AUDIO OUTPUT 600 OHM Interface Connector: RCA Type Phono Jack
 PSQ-2910
 Input Voltage: 80 - 250 VAC
 Input Frequency: 40 - 400 Hz
 Output Voltage: 9 VDC
 Supply Current: 1 A
 Output Power:9 W
 
             
          
 
      