Honeywell Power HPF-PS6/HPF-PS10 Fire Alarm Power Supply
The Honeywell Power HPF-PS6/HPF-PS10 fire alarm power supply provides 24 VDC notification and auxiliary power with integrated battery charging. Choose the HPF-PS6 for 6A total capacity and five outputs, or the HPF-PS10 for 10A and seven outputs. Both models feature independently configurable circuits inside a red, locking steel enclosure.
Designed for professional fire alarm installations, these supplies support notification appliance circuits (NACs), four-wire smoke detectors, annunciators, and door holders. Select the 6 amp remote power supply for applications requiring fewer circuits. Choose the 10 amp battery charger supply when your design calls for additional current capacity and output connections. Each version supports constant or resettable auxiliary power.
Both versions accept 120 VAC input and interface with compatible 12V or 24V fire alarm control panels (FACPs). They support UL 864 panels using standard reverse-polarity notification circuits, plus synchronization for System Sensor, Wheelock, Gentex, and AMSECO appliances. Onboard configuration switches simplify setup, while individual circuit indicators and stored trouble history assist service technicians. Class A operation requires the separately sold ZNAC-PS converter card.
Model Options: Amperage and Output Differences
- HPF-PS6: 6A maximum combined continuous output, five independently configurable outputs, and two isolated control inputs.
- HPF-PS10: 10A maximum combined continuous output, seven independently configurable outputs, and three isolated control inputs.
- Current Allocation: Total capacity applies across all outputs combined. Individual terminal ratings depend on regulated or special-application operation.
Key Features
- Configurable Distribution: Assign inputs to outputs to accommodate notification, auxiliary, and door holder circuits.
- Flexible Circuit Wiring: Use Class B circuits or add the optional converter for Class A wiring without sacrificing outputs.
- Selectable Notification Patterns: Configure ANSI Temporal 3 or Temporal 4 coded operation for the application.
- Appliance Synchronization: Coordinate supported notification devices through panel signals, control modules, or cascaded supplies.
- Integrated Charging: Charge supported lead-acid batteries up to 33 Ah with an external battery cabinet.
- Service Diagnostics: Check individual power and trouble indicators, stored fault history, and dedicated trouble relays.
- Accessible Installation: Route wiring through ten double knockouts and remove the cabinet door for improved access.
- Onboard Setup: Configure operating functions through DIP switches without additional software.
Technical Specifications: Model-Specific Ratings
- HPF-PS6 Total Output: 6A maximum continuous, combined across five circuits.
- HPF-PS6 Control Inputs: Two fully isolated circuits.
- HPF-PS6 AC Input: 120 VAC, 50/60 Hz; 5A maximum.
- HPF-PS6 Regulated Terminal Ratings: TB8-TB9: 1A per circuit; TB10-TB12: 0.3A per circuit.
- HPF-PS10 Total Output: 10A maximum continuous, combined across seven circuits.
- HPF-PS10 Control Inputs: Three fully isolated circuits.
- HPF-PS10 AC Input: 120 VAC, 50/60 Hz; 6.2A maximum.
- HPF-PS10 Regulated Terminal Ratings: TB8-TB11: 1.5A per circuit; TB12-TB14: 0.3A per circuit.
- Special-Application Terminal Rating: Both models support up to 3A per output, subject to the combined model limit.
Technical Specifications: Shared Electrical Features
- Output Voltage: 24 VDC, filtered.
- Output Configuration: Class B or optional Class A; resettable or non-resettable auxiliary power.
- Class A Accessory: ZNAC-PS converter card, sold separately.
- Trigger Voltage: 9-32 VDC.
- Trigger Current Per Input: 1 mA at 9-16V; 2 mA at 16-32V.
- Trouble Relays: Two Form C relays for AC and general trouble; normally closed contacts.
- Trouble Contact Rating: 4A at 24 VDC.
- End-of-Line Supervision: Normal resistance range of 2-27 kilohms.
- Earth Fault Detection: Selectable enabled or disabled operation.
- AC Trouble Reporting: Delay timer.
- Cascading: Up to four supplies.
- Supply Wiring: 12-14 AWG with 600V insulation.
- Removable Terminal Capacity: Accepts wire up to 12 AWG.
Battery Charging and Cabinet Specifications
- Battery Chemistry: Lead-acid only.
- Float-Charge Voltage: 27.6 VDC.
- Maximum Charging Current: 1.5A.
- Internal Battery Accommodation: Two 7 Ah or two 18 Ah batteries.
- Maximum Charging Capacity: 33 Ah with batteries in a separate cabinet.
- Charger Control: DIP-switch disable function supports applications using an external charger.
- Enclosure: Locking steel cabinet with powder-coated finish, removable door, and ten double knockouts.
- Color: Red.
- Dimensions: 20" H x 14.5" W x 3.5" D.
- Configured Weight: 24 lb with two 7 Ah batteries; 39 lb with two 18 Ah batteries.
- Standards: NFPA 72; UL 864 in NAC expander mode; UL 1481.
- Published Approvals: UL listing S24562; CSFM 7315-1637:0505; FDNY COA 2022-TMCOAP-002231-AMND; FM Approved. Approval applicability depends on configuration.