Kidde KIR-OSD Optica Intelligent Addressable Photoelectric Smoke Detector
Estimated Shipping Widget will be displayed here!
Condition: New
Description
Kidde KIR-OSD Optica Intelligent Addressable Photoelectric Smoke Detector
The Kidde KIR-OSD Optica Intelligent Addressable Photoelectric Smoke Detector is a rotary-addressed fire detection device designed for compatible Kidde FX Series fire alarm systems. Using multi-criteria optical sensing technology, it analyzes airborne particles to identify smoke while reducing nuisance alarms caused by common environmental conditions, including cooking-related particulates and steam.
Designed for commercial buildings, offices, educational facilities, healthcare environments, and professional fire alarm installations, the KIR-OSD combines dual-wavelength optical sensing with multiple detection angles to improve smoke recognition. Its onboard microprocessor processes sensor readings through digital filtering algorithms, helping distinguish combustion-related smoke from non-fire particles. Five programmable sensitivity settings and 20 pre-alarm configurations provide flexibility for different installation environments. Automatic day/night sensitivity adjustments allow compatible fire alarm control panels to adapt detection parameters to changing occupancy conditions. The detector also supports up to 250 intelligent device addresses per compatible signaling loop, making it suitable for larger addressable fire alarm networks.
The KIR-OSD integrates with Kidde fire alarm control panels equipped with an Intelligent Loop controller, including compatible FX Series systems. Rotary address switches simplify device identification, while automatic self-diagnostics and non-volatile memory preserve operational and maintenance information. Two environmental compensation levels and two dirty-detector warning levels help identify conditions requiring maintenance. A bicolor LED provides local status indication. The detector supports standard, relay, fault-isolator, and audible mounting bases for flexible system integration. Listed to UL 268 7th Edition, UL 268A, and CAN/ULC-S529, the KIR-OSD provides addressable smoke detection for professionally designed fire alarm systems.
Key Features
- Multi-Criteria Optical Smoke Detection: Uses dual optical wavelengths and multiple sensing angles to identify smoke particles while helping reject common nuisance sources.
- Intelligent Addressable Communication: Integrates with compatible Kidde FX Series fire alarm panels and supports up to 250 intelligent device addresses per signaling loop.
- Adjustable Detection Sensitivity: Offers five sensitivity settings and 20 pre-alarm configurations to accommodate different monitored environments and system requirements.
- Automatic Environmental Compensation: Provides two compensation levels and two dirty-detector warning levels to support consistent operation and preventive maintenance.
- Rotary Device Addressing: Features integrated address switches for assigning detector addresses from 1 to 125 without additional programming hardware.
- Continuous Self-Diagnostics: Monitors detector condition and stores diagnostic information in non-volatile memory for maintenance and troubleshooting.
- Automatic Day/Night Adjustment: Allows compatible control systems to modify smoke sensitivity according to programmed operating schedules.
- Flexible Mounting Compatibility: Supports standard, relay, fault-isolator, and audible detector bases for commercial fire alarm installations.
Technical Specifications
- Brand: Kidde Commercial
- Manufacturer Part Number: KIR-OSD
- Distributor Part Number: ED-KIROSD
- Product Series: Optica
- Product Type: Intelligent Addressable Photoelectric Smoke Detector
- Detector Configuration: Rotary Addressed
- Sensing Technology: Multi-Criteria Optical/Photoelectric
- Optical Sensing: Dual-Wavelength, Multiple Detection Angles
- Signal Processing: Microprocessor-Based Digital Filtering
- Detection Medium: Airborne Smoke Particles
- Smoke Sensitivity Range: 0.5 to 4.36% per ft Obscuration
- Selectable Sensitivity Settings: 5
- Pre-Alarm Settings: 20
- Environmental Compensation: Automatic, 2 Levels
- Dirty Detector Warning Levels: 2
- Automatic Day/Night Sensitivity Adjustment: Supported
- Self-Diagnostics: Automatic
- Diagnostic Storage: Non-Volatile Memory
- Device Addressing: Dual Rotary Address Switches
- Address Range: 1 to 125
- Maximum Intelligent Device Addresses per Loop: 250, Subject to Control Panel Compatibility
- Connectivity: Wired
- Communication Type: Intelligent Digital Communication
- Compatible Control Systems: Kidde Fire Alarm Panels Using an Intelligent Loop Controller
- Compatible Panel Series: Kidde FX Series
- Operating Voltage: 15.20 to 19.95 VDC
- Normal Operating Current: 43 Microamperes
- Alarm Current: 70 Microamperes
- Operating Temperature: 32 to 120 Degrees F
- Storage Temperature: -4 to 140 Degrees F
- Operating Relative Humidity: 0% to 93%, Non-Condensing
- Air Velocity Range: 0 to 4000 ft/min
- Vibration Frequency Range: 10 to 35 Hz
- Vibration Amplitude: 0.01""
- Maximum Wall-Mounting Distance from Ceiling: 12""
- Mounting Configuration: Ceiling or Wall with Compatible Detector Base
- Housing Material: High-Impact Engineering Polymer
- Housing Color: White
- Status Indicator: Bicolor Green/Red LED
- Compatible Standard Bases: KI-SB, KI-SB4
- Compatible Relay Bases: KI-RB, KI-RB4
- Compatible Fault-Isolator Bases: KI-IB, KI-IB4
- Compatible Audible Bases: KI-ABST, KI-ABDT, KI-ABLT
- Compatible Remote Alarm Indicator: GSA-LED with KI-SB or KI-SB4 Base
- Compatible Detector Testing Equipment: Testifire 1000, Testifire 2000
- Compatible Mounting Boxes: North American 1-Gang, 3.5"" Octagonal, 4"" Octagonal, and Supported 4"" Square Electrical Boxes
- Supported Wiring Sizes: 12, 14, 16, and 18 AWG Through Compatible Detector Bases
- Recommended Wiring Sizes: 16 or 18 AWG
- Maximum Wiring Resistance: 10 Ohms per Wire
- UL Certification: UL 268 7th Edition, UL 268A
- Canadian Certification: CAN/ULC-S529
- Additional Listing: CSFM
- Country of Origin: China
- UPC: 793016061157
Installation and Compatibility
The Kidde KIR-OSD requires a compatible Kidde Intelligent Loop controller and an appropriate detector mounting base. Installers assign a unique device address through the two rotary switches located on the detector. The control panel can identify duplicate addresses during system configuration.
Compatible mounting bases include the KI-SB and KI-SB4 standard bases, KI-RB and KI-RB4 relay bases, and KI-IB and KI-IB4 fault-isolator bases. Supported audible bases include the KI-ABST, KI-ABDT, and KI-ABLT. Base selection depends on the system design, required signaling functions, and mounting configuration.
The detector is intended for professionally designed addressable fire alarm systems. Installation, testing, wiring, and maintenance must follow the manufacturer's instructions, applicable fire alarm standards, and local authority requirements. Advanced features such as sensitivity adjustment, pre-alarm functions, and maintenance reporting depend on the connected control panel.
"